Regulation 7(2) of the Building Regulations 2010 restricts the use of combustible materials in the external walls of certain buildings in England. Equivalent restrictions apply in Scotland under Regulation 8(3) of the Building (Scotland) Regulations 2004, and in Wales under the Building Regulations 2010 as amended by Welsh-specific secondary legislation. The required standard, A2-s1,d0 or A1 at 11m and above,is the same in all three jurisdictions.
| England | Scotland | Wales | |
|---|---|---|---|
| Legal instrument | Regulation 7(2), Building Regulations 2010 (as amended) | Regulation 8(3), Building (Scotland) Regulations 2004 (SSI 2022/136, in force June 2022) | Regulations 6(3) and 7(2), Building Regulations 2010 as amended by Building (Amendment) (Wales) Regulations 2025 (in force December 2025) |
| Height threshold | Above 11m (floor of highest storey) | Storey at 11m or above | Above 11m |
| Classification required | A2-s1,d0 or A1 | A2-s1,d0 or A1 | A2-s1,d0 or A1 | Metal composite ban | All buildings | All buildings | All buildings (from December 2025) | Key difference | BS 8414 desktop assessment route available in some cases | BS 8414 system test route removed for residential over 11m - component classifications must be complete | Broadly aligned with England; hostel, hotel and boarding house added to scope from December 2025 |
For relevant buildings, the external wall must use materials achieving at least A2-s1,d0. This applies to cladding panels, insulation in the external wall, and specified attachments such as balconies.
| Building Type | Height Threshold | Requirement |
|---|---|---|
| Dwelling, institution, residential care, hospital, school, assembly and recreation | Above 11m | Regulation 8(3), Building (Scotland) Regulations 2004 (SSI 2022/136, in force June 2022) |
| Higher-risk buildings (residential, 18m and above) | Above 11m (floor of highest storey) | A2-s1,d0 or A1 - also subject to Building Safety Regulator gateway process |
| Non-residential | No blanket restriction -[ boundary distance and unprotected area route available | Varies; consult AD B |
Under Regulation 8(6) of the Building (Scotland) Regulations 2004, a relevant building is one having a storey at 11m or above containing a place of assembly, entertainment or recreation; a residential care building or sheltered housing complex; a shared multi-occupancy residential building; a hospital; or a school. Single dwellings have separate provisions but the A1 or A2 requirement applies at 11m for the external wall of a high-rise domestic building.
Scotland removed the BS 8414 system testing route for residential relevant buildings above 11m. Component classifications alone must be complete. This is stricter than the England position.
Wales applies the same building types and height thresholds as England. The Building (Amendment) (Wales) Regulations 2025, in force December 2025, extended the existing prohibition to include hostels, hotels and boarding houses, and introduced a blanket ban on relevant metal composite materials on all buildings regardless of height.
Fire-retardant treated timber products may claim improved classification but any such claim must be evidenced by a current Declaration of Performance for the specific product and treatment.
Timber is in the Dalply range via Parklex Prodema, which achieves B-s1,d0. This does not meet the A2-s1,d0 requirement for relevant buildings above 11m in any of the three GB jurisdictions, without specific system test evidence. This is stated plainly because it matters.
If yes to all four, the restriction applies and external wall materials must achieve A2-s1,d0 or A1. The specific legal instrument varies by jurisdiction; confirm with the building control authority or verifier for the project.
Regulation 7(2) of the Building Regulations 2010 restricts the use of combustible materials in the external walls of relevant buildings above 11m in England. Equivalent restrictions apply in Scotland under Regulation 8(3) of the Building (Scotland) Regulations 2004 and in Wales under the Building Regulations 2010 as amended.
Combustible cladding is restricted in the external walls of relevant buildings above 11m in England, Scotland and Wales under separately legislated instruments. The required classification – A2-s1,d0 or A1 – is consistent across all three. Northern Ireland is governed by the Building Regulations (Northern Ireland).
Buildings in the relevant purpose groups with a storey at or above 11m must use external wall materials achieving A2-s1,d0 or A1. This applies across England, Scotland and Wales, though the precise triggering language differs between the three regulatory instruments. Height is measured to the floor of the highest storey.
Building height for the purposes of the cladding restrictions is measured from finished ground level to the floor of the highest storey. It is not measured to the roof ridge, eaves or parapet top.