A2-s1,d0 Explained: Euroclass Fire Classification For Façade Specifiers

What is A2-s1,d0?

A2-s1,d0 is a Euroclass reaction to fire classification under BS EN 13501-1. The string has three parts: A2 is the main class (limited combustibility); s1 describes smoke production (very low); d0 describes flaming droplets (none). It is the minimum classification required for cladding panels on the external walls of relevant buildings over 11m across England, Scotland and Wales.

The Classification System

Class Description Typical Materials
A1 Non-combustible. No contribution to fire. A2-s1,d0
A2 Limited combustibility. Very limited contribution in the SBI test. Reconstituted stone, aluminium composite with mineral core, some GFRP
B Combustible but very limited fire contribution. Does not spread flame significantly. Some GFRP composites, some timber composites
C to F Higher combustibility levels. Not permitted on relevant buildings above 11m. Untreated timber, most plastics, standard HPL

The s Suffix: Smoke Production

Class Meaning
s1 Very low smoke production. Required alongside A2 for relevant buildings over 11m in England, Scotland and Wales.
s2 Limited smoke production. Not permitted with A2 on relevant buildings over 11m.
s3 No limit. Not relevant for external wall cladding on relevant buildings.

The d Suffix: Flaming Droplets

Class Meaning
d0 No flaming droplets or particles. Required alongside A2-s1 for relevant buildings.
d1 No droplets persisting beyond 10 seconds. Not permitted.
d2 No limit. Not relevant.

Why A2-s1,d0 is The Threshold That Matters

The requirement for A2-s1,d0 or A1 on the external walls of relevant buildings above 11m is in force across all three GB jurisdictions, though the legal instrument differs in each:

  • England: Regulation 7(2), Building Regulations 2010 as amended
  • Scotland: Regulation 8(3), Building (Scotland) Regulations 2004 as amended by SSI 2022/136 (in force June 2022)
  • Wales: Regulations 6(3) and 7(2), Building Regulations 2010 as amended by the Building (Amendment) (Wales) Regulations 2025 (in force December 2025)

 

A product achieving A2-s1,d0 satisfies the classification requirement in all three jurisdictions.

England – View Approved Document B

Scotland – View Building (Scotland) Regulations 2004, Regulation 8

Wales – View Approved Document B Wales

What the Classification Does Not Tell You

Critical: A Euroclass classification is a property of the panel material. It does not cover the insulation, cavity barriers, fixings or subframe. A compliant panel does not make a compliant wall.

  • Fire performance of the insulation behind the panel.
  • Fire resistance of cavity barriers.
  • Classification of subframe brackets and fixings.
  • Performance of the complete external wall build-up as a system.

How To Verify a Claimed Classification

  • The Declaration of Performance must be current and not superseded.
  • The classification must cover the specific variant and thickness being specified.
  • The test standard must be EN 13501-1 – not an older national standard.
  • The classification must be reaction to fire, not fire resistance.

Dalply Systems and Their Euroclass Classifications

System Material Euroclass Certification
Petrarch (A1 Variants) Reconstituted Stone A2-s1,d0 DoP, BBA certificate
Petrarch (A2 Variants) GFRP Composite A2-s1,d0 DoP, BBA certificate
ForMe SKIN Aluminium A2-s2,d0 Declaration of Performance
ForMe Battens 50 Aluminium A2-s2,d0 Declaration of Performance
Steni Nature A2 Medium GFRP Composite A2-s1,d0 Declaration of Performance
Steni Colour, Vision, Terra GFRP Composite B-s1,d0 Declaration of Performance
Parklex (NATURCLAD) Timber Composite B-s1,d0 Declaration of Performance
GRC Panels Glass Reinforced Concreate A1 Declaration of Performance
Natural Stone Natural Stone A1 Declaration of Performance

Euroclass Fire Classification Frequently Asked Questions

What does A2-s1,d0 mean?

A2-s1,d0 is a Euroclass reaction to fire classification under BS EN 13501-1. A2 means limited combustibility; s1 means very low smoke production; d0 means no flaming droplets or particles.

Is A2-s1,d0 the same as non-combustible?

No. A1 is the non-combustible class. A2 is limited combustibility – a lower level of performance but one that satisfies the requirement for relevant buildings over 11m in England, Scotland and Wales.

What is the difference between A1 and A2?

A1 materials pass both the non-combustibility test and the gross heat of combustion test with no contribution to fire. A2 materials may have a very small combustible fraction but contribute minimally in the single burning item test. Both satisfy the external wall requirement.

Is a Euroclass rating enough to prove a façade is compliant?

No. A Euroclass classification covers the panel material only. Compliance with Approved Document B (England), the Scottish Technical Handbooks or Welsh Approved Document B requires evidence that the complete external wall build-up meets the requirements, not only the panel.