A2-s1,d0 is a Euroclass reaction to fire classification under BS EN 13501-1. The string has three parts: A2 is the main class (limited combustibility); s1 describes smoke production (very low); d0 describes flaming droplets (none). It is the minimum classification required for cladding panels on the external walls of relevant buildings over 11m across England, Scotland and Wales.
| Class | Description | Typical Materials |
|---|---|---|
| A1 | Non-combustible. No contribution to fire. | A2-s1,d0 |
| A2 | Limited combustibility. Very limited contribution in the SBI test. | Reconstituted stone, aluminium composite with mineral core, some GFRP |
| B | Combustible but very limited fire contribution. Does not spread flame significantly. | Some GFRP composites, some timber composites | C to F | Higher combustibility levels. Not permitted on relevant buildings above 11m. | Untreated timber, most plastics, standard HPL |
| Class | Meaning |
|---|---|
| s1 | Very low smoke production. Required alongside A2 for relevant buildings over 11m in England, Scotland and Wales. |
| s2 | Limited smoke production. Not permitted with A2 on relevant buildings over 11m. |
| s3 | No limit. Not relevant for external wall cladding on relevant buildings. |
| Class | Meaning |
|---|---|
| d0 | No flaming droplets or particles. Required alongside A2-s1 for relevant buildings. |
| d1 | No droplets persisting beyond 10 seconds. Not permitted. |
| d2 | No limit. Not relevant. |
The requirement for A2-s1,d0 or A1 on the external walls of relevant buildings above 11m is in force across all three GB jurisdictions, though the legal instrument differs in each:
A product achieving A2-s1,d0 satisfies the classification requirement in all three jurisdictions.
England – View Approved Document B
Scotland – View Building (Scotland) Regulations 2004, Regulation 8
Wales – View Approved Document B Wales
Critical: A Euroclass classification is a property of the panel material. It does not cover the insulation, cavity barriers, fixings or subframe. A compliant panel does not make a compliant wall.
| System | Material | Euroclass | Certification |
|---|---|---|---|
| Petrarch (A1 Variants) | Reconstituted Stone | A2-s1,d0 | DoP, BBA certificate |
| Petrarch (A2 Variants) | GFRP Composite | A2-s1,d0 | DoP, BBA certificate |
| ForMe SKIN | Aluminium | A2-s2,d0 | Declaration of Performance | ForMe Battens 50 | Aluminium | A2-s2,d0 | Declaration of Performance |
| Steni Nature A2 Medium | GFRP Composite | A2-s1,d0 | Declaration of Performance |
| Steni Colour, Vision, Terra | GFRP Composite | B-s1,d0 | Declaration of Performance |
| Parklex (NATURCLAD) | Timber Composite | B-s1,d0 | Declaration of Performance |
| GRC Panels | Glass Reinforced Concreate | A1 | Declaration of Performance |
| Natural Stone | Natural Stone | A1 | Declaration of Performance |
A2-s1,d0 is a Euroclass reaction to fire classification under BS EN 13501-1. A2 means limited combustibility; s1 means very low smoke production; d0 means no flaming droplets or particles.
No. A1 is the non-combustible class. A2 is limited combustibility – a lower level of performance but one that satisfies the requirement for relevant buildings over 11m in England, Scotland and Wales.
A1 materials pass both the non-combustibility test and the gross heat of combustion test with no contribution to fire. A2 materials may have a very small combustible fraction but contribute minimally in the single burning item test. Both satisfy the external wall requirement.
No. A Euroclass classification covers the panel material only. Compliance with Approved Document B (England), the Scottish Technical Handbooks or Welsh Approved Document B requires evidence that the complete external wall build-up meets the requirements, not only the panel.